10 Technical Data

10.1 AC1 Connection for Stand-Alone Grid

Rated power
Power for 30 minutes at 25°C
Power for 5 minutes at 25°C
Power for 1 minute at 25°C
Maximum AC power
for 3 s at 25°C
Maximum connectable power of the PV
inverters in off-grid systems
Rated grid voltage
Voltage range
Rated frequency
Frequency range
Frequency range of the set range
Rated current
Maximum output current as a peak
value for 60 milliseconds
Total harmonic distortion of the output
voltage (THD)
Displacement power factor cos φ
Recommended conductor cross-section
Maximum connectable conductor
cross-section
Cable diameter
Connection
Circuit breakers than can be tripped
Short circuit power of the device
Installation manual
Sunny Island
Sunny Island
3.0M
2,300 W
3,300 W
3,000 W
4,400 W
3,500 W
4,600 W
4,200 W
4,800 W
5,500 W
5,500 W
4,600 W
4,600 W
230 V
202 V to 253 V
202 V to 253 V
50 Hz
45 Hz to 65 Hz
45 Hz to 65 Hz
±5 Hz
10 A
60 A
˂ 4.5%
− 1 to +1
− 1 to +1
10 mm²
10 mm²
16 mm²
16 mm²
9 mm to 18 mm
9 mm to 18 mm
Lever terminal
Lever terminal
Trip characteristic
Trip characteristic
B6
13.8 kW
13.8 kW
Sunny Island
4.4M
6.0H
4,600 W
6,000 W
6,800 W
7,500 W
11,000 W
9,200 W
230 V
230 V
202 V to 253 V
50 Hz
50 Hz
45 Hz to 65 Hz
±5 Hz
±5 Hz
14.3 A
20.0 A
60 A
120 A
˂ 4.5%
˂ 4%
− 1 to +1
10 mm²
16 mm²
9 mm to 18 mm
Lever terminal
Trip characteristic
B6
B16 and C6
27.6 kW
SI30M-44M-60H-80H-IA-en-32
10 Technical Data
Sunny Island
8.0H
6,000 W
8,000 W
9,100 W
9,600 W
11,000 W
12,000 W
230 V
202 V to 253 V
50 Hz
45 Hz to 65 Hz
±5 Hz
26.1 A
120 A
˂ 4%
− 1 to +1
10 mm²
16 mm²
9 mm to 18 mm
Lever terminal
Trip characteristic
B16 and C6
27.6 kW