Daikin BRC2E52C7 Installation Manual page 7

Wired remote controller
Hide thumbs Also See for BRC2E52C7:
Table of Contents

Advertisement

The sheath part in the remote controller case should be stripped following these instructions.
Peel the shield and sheath
Sheath stripping length:
● ±150 mm for top left outlet
● ±200 mm for top center outlet
Connect the terminals (P/P1, N/P2) of the remote controller to the terminals (P1, P2) of the
indoor unit. (P1 and P2 have no polarities.)
3-4-1 Rear outlet
Upper case
Wiring fixing
point
BRC2E52C7 / BRC3E52C7
4P368041-1
2014.02
PCB
Clamp
<Wiring fixing guideline>
Remote controller installation procedure
±10 mm
For easy wiring, it is better to
keep ±10 mm difference
between the length of the two
wires.
Cutting guideline
of the wiring
Indoor unit
P1
P2
Clamp
Cross-section
Secure the wiring at
the wiring fixing point
by using the attached
clamp.
Lower case
-
Installation manual