Single and Dual setpoint mode

17. Single and Dual setpoint mode
NOTE
● When a centralized controller is connected, the remote controller is forced to single setpoint
mode. It is not possible to change to dual setpoint mode.
● Switch between Single setpoint mode and Dual setpoint mode
● Single setpoint mode is set by selecting "Single SP"
● Dual setpoint mode is set by selecting "0°C" – "8°C"
17-1
Enable the Menu/Enter and Cancel
button. To enable, refer to
Enable/disable the Menu/Enter and
Cancel button" on page
17-2
Press and hold the Cancel button for
4 seconds or longer. The Service
Settings menu is displayed.
17-3
Select
Min Setpoints Differential
and press the Menu/Enter button.
The "Min Setpoints Differential"
screen is displayed.
17-4
Select "None", "Single SP" or
"0°C" – "8°C" by using the
Down) buttons.
17-5
Press the Menu/Enter button. The
confirmation screen is displayed.
17-6
Select
Yes
and press the Menu/
Enter button. The settings are
confirmed and the Service Settings
menu returns.
17-7
Press the Cancel button once. The
remote controller restarts and the
Basic screen returns.
Installation manual
39
"4-2
12.
17-2
17-3
17-4
(Up/
17-5
17-6
<Basic screen>
28
°C
<Service Settings>
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Min Setpoints Differential
External Input Interlock
Group Address
Return
Setting
Min Setpoints Differential
Min Setpoints Differential
Single Sp
Return
Setting
Min Setpoints Differential
Save the settings?
Yes
No
Return
Setting
<Service Settings>
BRC2E52C7 / BRC3E52C7
Press and hold the Cancel
button for 4 seconds or
longer while the backlight
is lit.
Press the Menu/Enter
button.
Press the Menu/Enter
button.
Press the Menu/Enter
button.
4P368041-1
2014.02