17-8
Disable the Menu/Enter and Cancel
button when no other settings need
to be changed. To disable, refer to
"4-2 Enable/disable the Menu/Enter
and Cancel button" on page
NOTE
● In Single setpoint mode both cooling and heating setpoints are the same. Changing one
setpoint automatically changes the other setpoint.
● In Dual setpoint mode there is always a limitation for the heating and cooling setpoint:
- Cooling setpoint ≥ heating setpoint + minimum setpoints differential.
When the cooling setpoint is lowered below the heating setpoint + minimum setpoints
differential, the heating setpoint is automatically lowered.
- Heating setpoint ≤ cooling setpoint – minimum setpoints differential.
When the heating setpoint is increased above the cooling setpoint – minimum setpoints
differential, the cooling setpoint is automatically increased.
18. Other Service Settings
18-1 Group Address
● Assign the group address and unit number for centralized control.
● The group and unit address can only be set when a centralized controller is connected.
This menu is only visible when a centralized controller is connected.
● The group and unit address can be "set" and "released".
NOTE
Don't forget to release the group address before disconnecting the centralized controller because
the menu will not be accesible afterwards.
18-2 Indoor and outdoor unit Airnet Address
● Set the indoor and outdoor unit Airnet Address.
18-3 Indoor Unit Status
● Consult the indoor unit thermistor temperatures.
Th1
Th2
Heat exchanger thermistor
Th3
Th4
Th5
Th6
BRC2E52C7 / BRC3E52C7
–
4P368041-1
2014.02
12.
SkyAir
Suction air thermistor
-
Discharge air thermistor
-
-
VRV
Suction air thermistor
Heat exchanger liquid pipe thermistor
Heat exchanger gas pipethermistor
Discharge air thermistor
-
-
Other Service Settings
Installation manual
40