This message indicates that a fan has failed, and that service is required. Because the
fans of the rectifier/battery charger and the inverter are redundant, the load is still
supplied by the inverter.
This message indicates that there is a fault in an auxiliary cabinet, and that service is required.
This message indicates that the battery may have reached its end of life (based on the rated
lifetime and the conditions of use).
This message indicates that the core controller of the selected module (UPS module or SSC,
see Section 2.2.2) is not sending data to the alphanumeric display. The status of the module
is still correctly indicated by the LEDs of the visible panel (see Section 2.2.1) and the hidden
panel (see Section 2.2.3).
This message indicates that the core controller of the selected module (UPS module or SSC,
see Section 2.2.2) is sending invalid data to the alphanumeric display. The status of the
module is still correctly indicated by the LEDs of the visible panel (see Section 2.2.1) and the
hidden panel (see Section 2.2.3).
This message indicates that the alphanumeric display is not operating properly. The status of
the UPS module or SSC is still correctly indicated by the LEDs of the visible panel (see
Section 2.2.1) and the hidden panel (see Section 2.2.3).
FAN FAILURE
CALL SERVICE
!
AUXILIARY CABINET FAULT
CALL SERVICE
!
CALL SERVICE FOR
BATTERY PM
!
MODULE NUMBER X
UNAVAILABLE
MODULE NUMBER X
FAULT
DISPLAY NUMBER X
UNAVAILABLE