EPS 6000 UPS Shared Systems
This pushbutton provides access to power and
frequency measurements, including:
ı
Battery pushbutton
This pushbutton provides access to battery measurements, including:
Alarms pushbutton
This pushbutton is used to display current alarms, or to display stored alarms.
If the alarm key is pressed repeatedly, the display will scroll through the stored
alarm record, returning to the latest after the oldest is shown.
If a blinking character (!) appears in the display, the user may press the Alarm
pushbutton again to scroll through additional useful information.
Ø
pushbutton
This pushbutton is reserved for future use.
°
Pushbutton
Depending on the displayed message, this pushbutton may serve to indicate confir-
mation, positive response, and other functions.
2 — 8
Inverter current
Load current
Percent current drawn by the load relative to UPS module or SSC rating
Crest factor per phase
Pushbutton
Main AC input (mains 1) frequency
Bypass AC input (mains 2) frequency
Inverter frequency
Power drawn by the load (in kW and kVA)
Load power factor
Battery voltage
Battery current
Battery ambient temperature
Battery time available
Battery time remaining
Operation