10.1. Boiler room recommendation

- Package ( boiler, burner, tank, feeder) should be placed in separate room, centrally to heated rooms
- Front door should open outside and must be made of nonflammable materials, with 0,8 width
- Floor should be made of nonflammable materials or covered with 0,7 mm steel plate at minimum 0,5 m distance
to door edges. Boiler should be located on a nonflammable foundation, lifted 0,05 m above floor level
- Boiler room should have artificial lightning but natural light is also recommended
- Distance to walls in boiler room should allow for easy access to all sides of the boiler
- Minimal distance from front side of the boiler to opposite wall should be 1m
- Minimal height of the boiler room: at least 2,2 m; in existing building it is allowed 1,9 m with assured
supply-exhaust ventilation.
- It is forbidden to install boiler and burner in damp rooms or with elevated humidity. Corrosion process
may in short time damage the boiler and burner.

10.2. Ventilation

- Boiler room should have 200 cm² supply-air duct
- Exhaust duct should have at least 14x14 cm section with inlet hole under boiler room ceiling that should
lead above roof and be placed near chimney.
- Ventilation ducts should be made of nonflammable materials.
- It is forbidden to install mechanical ventilation
ATTENTION!
High risk of carbon monoxide poisoning exists if boiler is located in a room with insufficient access to fresh air.

10.3. Chimney system

Chimney draft:
If the chimney draft is exceeding 15 Pa, a draft stabilizer should be mounted in the chimney.
WARNING!
By chimney temperatue less than 180°C at rated output, you should be aware that smoke dose not
condense in the chimney as it gives soot. At particularly low smoke temperature it may be necessary to
put a ceramic or stainless steel sleeve in the chimney.
pic. Exemplary boiler connection to stainless steel chimney