About this operating manual 1.3 Symbols and identification markings This operating manual is part of the unit. Identification of warnings ► B efore working on or with the unit read the operating manual carefully and follow it for all Symbol Meaning activities at all times, especially the warnings and safety instructions.
1.4 Contact – Heating installer – Plumbing installer Addresses for purchasing accessories, for service – Refrigeration system installer (maintenance cases or for answers to questions about the unit and work) this operating manual can be found on the internet at any time and is kept up-to-date: ●...
Injuries and environmental damage due to If a system is not planned, designed, started up and operated according to the given requirements, there refrigerant is a risk that the following damage and faults will The unit contains harmful and environmentally occur: dangerous refrigerant. If refrigerant leaks from the ●...
Description 1 Overflow valve Valve motor 3-way changeover valve, heating 3.1 Layout circuit/domestic hot water Heating circuit/hot water circulation pump NOTE Module box This section essentially names Height-adjustable foot (4x) components relevant for fulfilling the tasks described in this operating manual. Electrical switch cabinet Heating element Housing with unit components...
Page 7
Module box, variant without cooling Module box, variant with cooling Compressor Compressor Condenser Condenser Vibration isolator (4x) Vibration isolator (4x) Lifting lug (4x) Lifting lug (4x) Evaporator Evaporator Heat source circulation pump Heat source circulation pump 7 Heat source filling and drain tap 7 Heat source filling and drain tap 8 Heating filling and drain tap 8 Heat source filling and drain tap 9 Heating filling and drain tap...
Control unit ● Room thermostat for switching the cooling function (if included) ● Dew point monitor for protecting a system with cooling function at low flow temperatures ● Expansion board for automatic changeover between heating and cooling mode ● Manual output control heating element (MLRH) for limiting the output of the electric heating element ●...
4.2 Maintenance Cooling Cooling is integrated in type K units. Type H units Wipe down the outside of the unit only using a damp can be retrofitted with the “Cooling package” cloth or cloth with mild cleaning product (washing- accessories. The following options are possible for up liquid, neutral cleaning product).
5.2 Storage Unpacking ► W here possible do not unpack the unit until NOTE directly before installation. If the unit is not transported by a pallet truck: ► Store unit protected against: Do not lift off the pallet until after unpacking – Moisture/damp and dismantling the housing panels. –...
5.4 Installation Transport with a handcart Installation room and space requirements NOTE ● If transporting with a handcart the module box must be pushed in. NOTE ● This figure with the handcart shows Note and follow the local regulations and transporting the unit on its left-hand side;...
Installation and connection ► Unit without cooling: 6.1 Dismantle the module box ATTENTION If the module box is tilted by more than 45°, compressor oil runs into the cooling circuit. ► Do not tilt the module box by more than 45°. NOTE ●...
Page 13
Use a spanner to close the shut-off valves of the Disconnect the electrical connections: heat source (behind the covers). – Disconnect 2 white connectors (1) at the bottom of the electrical control cabinet. To do this, release the lugs by pressing on the sides of the connectors.
Page 14
Use spanner size SW 37 to unscrew the heating 12. To protect the floor and move the module box (3) flow. more easily: place boards“(4) under it, e.g. from the packaging material. 13. Lift and hold nut (1) on the heating flow. 14. Slowly and carefully pull out the module box by the carrying lugs“(2). Ensure that none of the pipes are damaged 10.
6.2 Installing the module box Install the compression fittings and ball valves Place the module box carefully in the bottom of the housing and slowly and carefully push it in. NOTE – Lift and hold nut on the heating flow. This section is only relevant for units with up – Lift up pipes so that they do not get damaged. to 12 kW capacity.
6.4 Connect the electrical cables Pull in the cables and conductors and make the connections ATTENTION Strip the sheathing of all cables to the external loads before laying in the cable duct of the Irreparable damage to the compressor due to control box. wrong rotating field! Open electrical switchbox: ►...
6.5 Installing the control Use cable ties ( separate pack) to fix the LIN bus cable to a web of the masking plate around 20 cm in front of the connector (strain relief). NOTE The control can be inserted in a recess in the front panel of the unit or can be installed on the wall.
7.2 Heating water quality Feed in the cables from the wall (e.g. in-wall box) or from below. Route the LIN bus cable from the top right-hand NOTE side at the rear from the heat pump and plug into ● For detailed information refer, among the control at the bottom.
7.4 Vent the circulation pump of the Mix antifreeze with water thoroughly with the required ratio, before adding to the heat source. heat source C heck the concentration of the water-antifreeze mixture. Frost protection: -13 °C NOTE Fill the heat source with the water-antifreeze The diagram shows the unit variant with mixture.
7.5 Flush and fill the heating and Position the valve motor (1) on the 3-way changeover valve (3). domestic hot water charging I nsert the U-clip (2) into the floor of the valve circuit motor. Drain pipe of the safety valve is connected. The front panel of the module box is unscrewed. ...
Set the overflow valve NOTE ● The activities in this section are only necessary for in-line tank integration. ● Complete the worksteps quickly, other- wise the maximum return temperature can be exceeded and the heat pump ► Open the overflow valve fully, close heating cir- switches to high-pressure fault. cuits ● Turn the adjusting knob at the overflow ►...
11.2 Maintenance as required – The electrical installation has been carried out properly according to this operating ● Yearly, more frequently if necessary: manual and local regulations. – Checking and cleaning the components of – The power supply for the heat pump is the heating circuit and the heat source, e.g.
Faults Dismantling and Disposal NOTE 13.1 Dismantling If the safety temperature limiter on the Unit is safely disconnected from the power electric heating element has tripped, no fault supply and protected against being switched is displayed. back on again. ► Read out the cause of the fault via the ►...
SWCV 62(H)(K)3, SWCV 162(H)(K)3 Dimensioned drawing ↑ ↓ ↓ ↑ ↓ >250 >250 Item Name Dim. Heating water outlet (flow) Ø28 Outside diameter Heat source inlet (in heat pump) Ø28 Pos. Bezeichnung Dim. optionally at the top, on the right or left Outside diameter Ø28 Heizwasser Austritt (Vorlauf)
Page 29
Dimensioned drawing of control, wall-mounted bracket Schutzvermerk ISO 16016 beachten Schutzvermerk ISO 16016 beachten Wall mounted Bohrschablone Blattformat: A4 hoch Maßstab Det. Maßstab Allgemein- Oberflächen toleranz Werkstoff Gewicht Datum Name Benennung Maßbild WZS 18.11.2014 Brueckner Erstellt Gepr. Norm. Ø6 Ø6 ait-deutschland GmbH ArtikelNr. Blatt 819447 Industriestraße 3 D - 95359 Kasendorf PEP 015-2014...
Installation plans 1000 > 1 Key: DE819452 V1 Version 1 FS Free space for service purposes FZ Free space for functionally necessary accessories OKF Finished floor level Legende: DE819452 All dimensions in mm. Version 1 Freiraum für Servicezwecke Freiraum für funktionsnotwendiges Zubehör Oberkante Fertigfussboden Subject to change without notice | 83057000bUK –...
Page 31
Installation plans 1000 > 1 Key: DE819452 V2 Version 2 FS Free space for service purposes FZ Free space for functionally necessary accessories Legende: DE819452 OKF Finished floor level Version 2 Freiraum für Servicezwecke Freiraum für funktionsnotwendiges Zubehör Oberkante Fertigfussboden All dimensions in mm. Alle Maße in mm.
Page 32
Installation plans > 1 > 1 Key: DE819452 V3 Version 3 FS Free space for service purposes Legende: DE819452 OKF Finished floor level Version 3 Freiraum für Servicezwecke Oberkante Fertigfussboden 1000 Alle Maße in mm. All dimensions in mm. Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Hydraulic integration, unit variant H (heating) Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 34
Hydraulic integration, separate buffer tank, unit variant H (heating) Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 35
Hydraulic integration, unit variant K (cooling) Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 36
Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
SWCV 62(H)(K)3 Circuit diagram 1/3 brown blue brown brown Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 40
Circuit diagram 2/3 SWCV 62(H)(K)3 OUT4 OUT1 OUT6 OUT17 PWM1 PWM2 OUT14 OUT13 Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 41
SWCV 62(H)(K)3 Circuit diagram 3/3 blue NTC9 brown / blue white brown green yellow pink NTC12 NTC13 NTC14 white / blue grey / brown pink / brown violet grey / pink red / blue white / green Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 42
Circuit diagram 1/3 SWCV 162(H)(K)3 black black brown brown grey grey Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 43
SWCV 162(H)(K)3 Circuit diagram 2/3 OUT4 OUT1 OUT6 OUT17 PWM1 PWM2 OUT14 OUT13 Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 44
Circuit diagram 3/3 SWCV 162(H)(K)3 blue NTC9 brown / blue white brown green yellow pink NTC12 NTC13 NTC14 white / blue grey / brown pink / brown violet grey / pink red / blue white / green Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 45
Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
EC Declaration of Conformity EC Declaration of Conformity in accordance with the EC Machinery Directive 2006/42/EC, Annex IIA The undersigned confirms that the following designated device(s) as designed and marketed by us fulfill the standardized EC directives, the EC safety standards and the product-specific EC standards. In the event of modification of the device(s) without our approval, this declaration shall become invalid.
Page 47
Subject to change without notice | 83057000bUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
Page 48
GmbH Industriestraße 3 D-95359 Kasendorf E info@alpha-innotec.de W www.alpha-innotec.de alpha innotec – an ait-deutschland GmbH brand...