5 ASSEMBLY AND INSTALLATION OF THE BOILER

5.2 GENERAL CONDITIONS OF INSTALLATION

Only a person with valid authorization for installation and assembly of the heating technology
devices can install the boiler. The installation requires an appropriate project that is in line with
valid prescriptions. Technician must check the boiler before installing, if data given on the pro-
duction label are in conformity with data in the project and the documentation attached to the
boiler. The boiler connection must be in line with the valid prescriptions, norms, regulations and
this instruction manual.
WARNING: Producer takes no responsibility for damages caused by wrong connection
or operation!

5.3 BOILER PLACING

Boiler serves for installation and operation in the space with the basic environment (AA5/AB5)
according to STN 33 2000-3.
Boiler room must meet the following requirements:
 Boiler is not suitable for use in the potentially explosive environment.
 The temperature in the boiler room must not drop below the freezing point.
 Boiler does not provide any lighting. Customer must ensure sufficient light source according
to the local norms and regulations.
 It is necessary to consult the installation with the producer, if the boiler will be installed at
height above sea level exceeding 1 800 m.
 Boiler room must have sufficient ventilation and inlet of the required burning air (minimally
10 cm
2
/kW of the boiler output). Hole for the ventilation should be designed to not let the
outside weather influence its function. (rain, snow, wind)
12

5.1 MANIPULATION WITH BOILER

Boiler is delivered on the pallet. Perform manipulation
with boiler only at the pallet. Put down the boiler form
the pallet immediately at the place of installation. It is
possible to perform this by use of manipulation cart or
by crane and handles, which are welded at the ex-
changer of the boiler.
Figure 1 Manipulation with boiler with use of the
welded handles