Pinnacle 2 and 4 Flavor Service Manual
Each freeze cylinder defrost cycle will terminate either when the suction temperature reaches 50°F or it
will time out after 8 minutes. There may be 9 defrost times scheduled for each of the 7 days of the week.
Cylinder 1 will begin defrosting at the set defrost time. Cylinder 2 will begin defrosting 30 minutes after
cylinder 1 began defrosting. There are no defrosts programmed from the factory.
To set defrost times:
1. Press <DAY> to select 1 of 8 options (SUNDAY, MONDAY, TUESDAY, WEDNESDAY, THURSDAY,
FRIDAY, SATURDAY, ALL DAYS).
2. Press <GO> to advance to the SET DEFROST TIME menu.
3. Press <NEXT> to change the field from HOURS to MINUTES.
4. Press <UP> and <DOWN> to change the setting in the fields.
5. Press <BACK> to save the changes.
6. If desired, repeat steps 2–5 to set more defrost times for the selected day.
7. If desired, repeat steps 1–6 to select different days and times.
© 2003-2014, Cornelius Inc.
- 22 -
Publication Number: 560007298SER