Minimum Clearances To Combustibles - Superior DRL3042TEN Installation And Operation Instructions Manual

Drl3000 linear direct-vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
Superior™ DRL3000 Linear Direct-Vent Gas Fireplaces

MINIMUM CLEARANCES TO COMBUSTIBLES

Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8), with the
following exceptions:
When unit is recessed, the side walls surrounding the unit must not extend beyond unit front edge (Figure 6).
When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend
beyond the front edge of the unit (Figure 6).
Table 8: Minimum Clearances *
clearance immediately in front of viewing area(s)
* 3" (76 mm) above any horizontal/inclined vent component.
** See Page 20 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
Hearth Extension
A hearth extension is not required with this fireplace. If a hearth extension is used, do not block the lower control
compartment door. Any hearth extension used is for appearance only and does not have to conform to standard
hearth extension installation requirements.
Shelf Height
The venting attached to the top vent should be routed in a way to minimize obstructions to the space above the
fireplace. Do not insulate the space between the fireplace and the area above it (Table 9). The minimum height from
the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is
shown in Table 9.
NOTE: This is a heat-producing appliance. Objects placed above the unit are exposed to elevated temperatures.
Table 9: Combustible Shelf Height—Top Vent
* 6" straight vent section required before 90° elbow
** Includes 3" clearance to combustibles required above vent components
Top Spacers
From Bottom of Unit to Ceiling
Front Service Clearance—
Model
Secure Vent
42" *
51 1/4" (1299 mm)
54" *
55" (1400 mm)**
1/2" (13 mm) to wrapper
Back
0" (0 mm) to Spacers
1/2" (13 mm) to wrapper
Sides
0" (0 mm) to Spacers **
0" (0 mm)
Floor
0" (0 mm)
65" (1651 mm)
3" (76 mm)—Top *
Vent
1" (25.4 mm)—Sides and Bottom
36" (914 mm)
Top Vent with one 90° Elbow
Secure Flex
(flex elbow)
®
®
53" (1345 mm)
56 3/4" (1441 mm)**
Installation
900079-02 05/2015
No combustibles
or insulation
Shelf Height
in the shaded
(see table)
area between
the appliance
and the shelf
above it.
15