Minimum Clearances To Combustibles - Superior DRT2000 Series Installation And Operation Instructions For

Direct-vent gas fireplaces
Hide thumbs Also See for DRT2000 Series:
Table of Contents

Advertisement

Innovative Hearth Products
DRT2000 and DRC2000 Direct-Vent Fireplaces

MINIMUM CLEARANCES TO COMBUSTIBLES

Fireplace And Vent Clearances
The fi replace is approved with zero clearance to combustible materials on all sides (Table 8), with the following
exception: The unit may not be recessed (allowance made for mantel legs / side trim in Figure 6). When the unit is
installed with one side fl ush with a wall, the wall on the other side of the unit must not extend beyond the front edge
of the unit (Figure 6).
Table 8 - Minimum Clearances *
* 3" (77 mm) above any horizontal/inclined vent component.
** See Page 19 for clearance requirements to the nailing fl ange located at each side of the unit and any screw heads adjacent to it.
*** Top vent clearance can be reduced to 2" on horizontal runs when fi rst elbow is located at least 6 ft above the fi replace.
The fi replace must be mounted on a fully supported base extending the full width and depth of the unit. The fi replace
may be located on or near conventional construction materials. However, if installed on combustible materials, such
as carpeting, vinyl tile or other combustible material other than wood fl ooring, the appliance shall be installed on a
metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fi replace. If a hearth extension is used, do not block the lower control
compartment door. Any hearth extension used is for appearance only and does not have to conform to standard
hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models, the venting attached
to the top vent should be routed in a way to minimize obstructions to the space above the fi replace. Do not insulate
the space between the fi replace and the area above it (Tables 9 and 10). The minimum height from the base of the
fi replace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Tables
9 and 10.
Table 9 - Combustible Shelf Height—Top Vent
14
From Bottom of Unit to Ceiling
Front Service Clearance—
clearance immediately in front of viewing area(s)
Model
33" Models
35" Models
40" Models
45" Models
1" (26mm) to wrapper for 45" model, all
Back
others 1/2" (13mm) to wrapper
0" (0 mm) to Spacers
1/2" (13 mm) to wrapper
Sides
0" (0 mm) to Spacers **
Top Standoffs
0" (0 mm) to top standoffs
Floor
0" (0 mm)
64" (1626 mm)
3" (77 mm)—Top * ***
Vent
1" (26 mm)—Sides and Bottom
36" (914 mm)
Top Vent with one 90° Elbow
Secure Vent
®
Secure Flex
44" (1118 mm)
46" (1168 mm)
47" (1194 mm)
49" (1245 mm)
52" (1321 mm)
54" (1372 mm)
50" (1270 mm)
52" (1321 mm)
®
(fl ex elbow)
Shelf Height
(see table)
General Information
900004-00, 03/2017
No combustibles
or insulation
in the shaded
area between
the appliance
and the shelf
above it.

Advertisement

Table of Contents
loading

Table of Contents