WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 2 for wire
sizing information and maximum fuse or "HACR Type"
circuit breaker size. Each unit is marked with a
"Minimum Circuit Ampacity". This means that the field
wiring used must be sized to carry that amount of
current. Depending on the installed KW of electric heat,
there may be two field power circuits required. If this is
the case, the unit serial plate will so indicate. All
models are suitable only for connection with copper
wire. Each unit and/or wiring diagram will be marked
"Use Copper Conductors Only". These instructions
MUST BE adhered to. Refer to the National Electrical
Code (NEC) for complete current carrying capacity data
on the various insulation grades of wiring material. All
wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C
copper) for all models, including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a "Maximum Time Delay
Relay Fuse" or "HACR Type" circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
COMPONENT LOCATION
ELECTRIC
HEATERS
UNIT
MOUNTED
THERMOSTAT
LOCATION
DEHUMIDIFICATION
CONTROL
(OPTIONAL)
Manual 2100-523
Page
20 of 41
FIGURE 15
SIDE FIELD
WIRE
ENTRANCE
REMOTE
THERMOSTAT
TERMINAL
BLOCK
CIRCUIT
BREAKER
PANEL &
CONTROLS
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.
See "Start Up" section for information on three phase
scroll compressor start-ups.
The field wiring connections are located behind the top
and hinged panel in the circuit breaker panel. See
Figure 15.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS.
All Equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 3.
OPERATING VOLTAGE RANGE
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
The standard Climate Control Option X is a remote
thermostat connection terminal block. See Figure 17 for
wiring diagram. Compatible thermostats are listed in
Table 4.
The Climate Control Option G is an electronic, non-
programmable manual or auto changeover thermostat
with humidistat. The subbase of the thermostat is
factory wired to the front panel of the unit. See Figure
18 for wiring diagram. Compatible for use with Bard
CS2000A* Controller and Energy Recovery Ventilator.
The Climate Control Option E is an electronic,
programmable thermostat with humidistat. The subbase
of the thermostat is factory wired to the front panel of
INDOOR
the unit. See Figure 19 for wiring diagram. Compatible
BLOWER
for use with Energy Recovery Ventilator.
The Climate Control Option I is an electronic,
programmable thermostat with humidistat and a CO
controller. The subbase of the thermostat and CO
controller are factory wired to the front panel of the unit.
See Figure 20 for wiring diagram.
NOTE: On option X or G the CS2000A* (or other field
provided means to control ventilation) must be
LOWER
used if any of the motorized ventilation options
CONTROL
PANEL
are installed.
NOTE: Thermostats are shipped in the bottom of the
unit and must be mounted to the factory
mounted subbase at time of installation.