Hitachi RCI-1.0FSN3 Service Manual page 84

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

2 Unit installation
C A U T I O N
In case that the thermistors supplied with the Dx-Interface are not long enough, please make sure that the length
extension is properly done avoiding the sensing distortion and that the joint is properly insulated to avoid any
electrical failure.
N O T E
When fitting the thermistors, remember that they must be secured correctly by the special clamp, ensuring
the perfect contact between the pipe and thermistor. Cover it completely with insulation, like cork tape or pipe
insulation, depending on the location. Replace them if damaged during maintenance work.

Thermistor installation example
1
Liquid / gas pipe thermistor (factory supplied)
2
Thermistor holder (field supplied)
3
Thermistor lead wire (field supplied)
4
Insulation (field supplied)
C A U T I O N
The thermistor must be installed properly in order to
avoid water onto the thermistor.

Typical installation location
Must be installed in the coldest liquid line
Liquid pipe
A
point in the heat exchanger (prior the
thermistor
Gas pipe
Must be installed as close as possible to
B
thermistor
the heat exchanger refrigerant outlet.
72
SMGB0077 rev.0 - 01/2013
distributor).
1
2
3
4