4 Electrical wiring
Follow the steps below to connect the remote control cable or the
optional extension wire:
1 Pass the cable through the knockout hole in the cabinet.
2 Connect the cable to terminals A and B of the terminal strip
(TB).
3 Tighten the screw on terminals A and B.
4 Check that the cables are correctly secured.
Follow the steps below to connect the power cables to the terminal
strip (TB):
1 Where necessary, loosen the screws on terminals L1 and N on
the terminal strip (TB).
2 Connect the power cables to terminals L1 and N.
3 Tighten the screws on terminals L1 and N.
4 Check that the cables are correctly secured.
Follow the steps below to connect the communication cables between the outdoor and indoor unit to the terminal strip
(TB):
1 Where necessary, loosen the screws on terminals 1 and 2 on the terminal strip (TB).
2 Connect the communication cables to terminals 1 and 2.
3 Tighten the screw on terminals 1 and 2.
4 Check that the cables are correctly secured.
Follow the steps below to connect the earth wire to the earth connection in the electrical box:
1 Where necessary, loosen the screw on the earthing connection in the electrical box.
2 Connect the shielded part of the power supply earth wire and the signal wiring earth wire to the earth connection.
3 Tighten the screw on the earthing connection in the electrical box.
4 Check that the shielded part of the earthing cables are correctly secured.
Firmly secure the cables using a tie inside the electrical box.
RPI-(0.8-1.5)FSN4E Terminal board location
Cover the cables and the hole using a sealant to protect them from
condensation and insects.
1
Printed circuit board 1 (PCB1)
2
Printed circuit board 2 (PCB2)
3
Terminal board (TB)
140
SMGB0077 rev.0 - 01/2013