Hitachi RCI-1.0FSN3 Service Manual page 110

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

3 Piping work and
refrigerant charge
Cutting
Define the necessary length of pipe and add a few more centimetres to give yourself enough margin in case the cut has
to be repeated.
Cut the pipe using a pipe cutter.
C A U T I O N
Ensure the pipe cutter rollers remain perfectly seated on the
copper pipe.
Remove any internal burrs arising from the pipe cutter using a pipe
reamer.
C A U T I O N
While making the cut, slant the pipe downwards to prevent burrs or shavings from falling inside the pipe.
Do not use hand saws, circular saws, abrasive grinders or other tools that generate shavings.
Strictly follow national or local regulations regarding occupational health and safety.
Wear appropriate means of protection during cutting or brazing operations and installation (gloves, eye
protection, etc).
If the pipe is not to be immediately flared, protect the end of the
pipe using a suitable cap or high quality insulation tape.
CAUTION
Do not leave the ends of flared pipes unprotected.
98
SMGB0077 rev.0 - 01/2013