6 Optional functions
Element
Optional function
Cooling lower limit for setting
FC
temperature
Heating upper limit for setting
Fd
temperature
Not available
FE
PC-ART: Lock function for timer
FF
PC-ARF: Not available
Maintenance alarms
H1
PC-ARF: Not available
PC-ART: Automatic control
indication
H2
PC-ARF: Indication of hot start
PC-ART: Operating mode
change restriction
H3
PC-ARF: Not available
PC-ART: Operating modes for
the ventilation unit with energy
/ heat recovery
H4
PC-ARF: Not available
230
SMGB0077 rev.0 - 01/2013
Individual
Settings
Condition setting
setting
00
01
Lower limit +1 °C
02
Lower limit +2 °C
X
Lower limit +(03-
03-08
09
Lower limit +9 °C
10
Lower limit +10 °C
00
01
Lower limit -1 °C
02
Lower limit -2 °C
X
Lower limit -(03-
03-08
09
Lower limit -9 °C
10
Lower limit -10 °C
00
–
01
Use at 00 conditions
02
00
X
Activated function
01
(factory setting)
–
–
Use at 00 conditions
00
O
01
–
–
Use at 00 conditions
00
O
01
Operating mode
00
change disabled
(factory setting)
Operating mode set
O
01
by the central control
Unlimited operating
02
–
–
Use at 00 conditions
00
Air conditioning only
01
O
Air conditioning +
02
–
–
Use at 00 conditions
Standard
This function is used to define a lower
temperature setting limit for FAN/
COOL/DRY modes.
08) °C
Standard
This function is used to define an
upper temperature setting limit for
HEAT mode. PC-ARF: up to -12 °C
08) °C
Not available
–
Not activated
function
This function is used to lock timer
activation.
Not available
–
Display
This function is used to display or hide
maintenance alarms.
Hide
Not available
–
Display
This function is used to display or hide
the automatic control indication.
Hide
This function is used to configure
restrictions to the HEAT mode.
+ FAN mode
–
mode
Not available
–
This function is only available for the
Ventilation only
ventilation unit with energy / heat
recovery.
ventilation
Not available
–
Description