Hitachi RCI-1.0FSN3 Service Manual page 385

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

10 Servicing
5 Remove the wirings for the freeze protection thermistor, gas pipe thermistor, inlet air thermistor and the expansion
valve coil from the wiring outlet at the upper part. Also remove the wirings for the outlet air thermistor, auto-louver and
fan motor from the wiring outlet at the lower part.
6 Remove 2 screws fixing the electrical box to dismount it from the indoor unit body.
N O T E
If the unit with the expansion valve kit is used, regard "expansion valve coil" as "expansion valve relay cord."
Screw for
Electrical Box Cover

For RPK-(2.0-4.0)FSN(H)3M
1 Remove the front panel according to the "Removing Front Panel" chapter
2 Remove the terminal board cover and the electrical box cover according to "Removing Printed Circuit Board" chapter
3 Then, remove the power source wiring, the transition wiring and the wiring for the remote control switch from the
terminal board.
4 Remove the connectors (on the PCB1) for the freeze protection thermistor, gas pipe thermistor, inlet air thermistor,
outlet air thermistor, auto-louver, PCB for indication, PCB for receiver, fan motor and expansion valve coil.
5 Remove the wirings for the freeze protection thermistor, gas pipe thermistor, inlet air thermistor, fan motor and expansion
valve coil from the wiring outlet at the upper part. Also remove the wirings for the outlet air thermistor, auto-louver, PCB
for indication and PCB for receiver from the wiring outlet at the lower part.
6 Remove 2 screws fixing the electrical box to dismount it from the indoor unit body.
7 Remove the earth screw to disconnect earth wire between the heat exchanger and the electrical box.
8 Before remounting the electrical box, make sure to connect the connectors mentioned above. Then mount the electrical
box in the reverse procedure.
N O T E
If the unit with the expansion valve kit is used, regard "expansion valve coil" as "expansion valve relay cord."
Earth Screw
373
SMGB0077 rev.0 - 01/2013
Screw for
Terminal Board Cover
Electrical Box
Cover
Terminal Board Cover
and Switch Cover
Screw for Earth Wiring
Screw for
Electrical Box
Screw for
Electrical Box Cover
Earth Wiring
Screws for
Electrical Box
10