6 Optional functions
Element
Optional function
Cooling temperature
bb
compensation
Not available
bC
Not available
bd
Not available
bE
Not available
C1
Not available
C2
HA function (only for Japanese
C3
market)
Drain pump in heating mode
C4
Static pressure selection (RPI)
C5
Increasing fan speed (RCI,
RCIM, RCD)
PC-ART: increasing fan speed
PC-ARF: Hi speed at heating
C6
Thermo-OFF
Cancellation of the forced
compressor operation for at
C7
least three minutes
225
SMGB0077 rev.0 - 01/2013
Individual
Settings
Condition setting
setting
Standard setting.
00
No compensation
It decrease the
X
01
temperature -1ºC
It decrease the
02
temperature -2ºC
00
Not available
Use at 00 conditions
01
00
Not available
Use at 00 conditions
01
00
Not available
Use at 00 conditions
01
00
Not available
Use at 00 conditions
01
"- -"
Not available
permanent
00
Not available
O
Use at 00 conditions
01
Not activated
00
O
01
Activated function
Standard static
00
pressure (factory
01
High static pressure
O
02
Low static pressure
00
Not available
01
Hi Speed 1
02
Hi Speed 2
Not activated
00
O
01
Activated function
00
Activated function
O
Not activated
01
Description
This function is used to obtain longer
cooling periods.
function
This function is used to activate the
drain pump in heating mode.
set)
This function is used to increase the
fan speed on the indoor ducted units.
This function is used to change the
indoor units fan speed installed in high
(2)
ceilings.
(2)
PC-ARF: This function is used
function
to increase the fan speed when
the thermostat reaches the set
temperature in heating using function
C5.
Cancels function b3.