Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 63

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Sensor connection
(continued)
Strap-on temperature sensor and immersion temperature sensor
740
720
700
680
660
640
620
600
580
560
540
20
30
40
68
86
104
Supply temperature/return temperature in °C / °F
17A or 17B
17A or 17B
50
60
70
80
90
122
140
158 176
194 212
For measuring the return temperature.
Electrical connection
Connect in accordance with the
overview on page 58 and 59 and
the control panel wiring diagram.
Remove the plug from the sensor
cable.
Check the sensor
1. Disconnect the sensor from
2. Measure resistance of sensor at
3. Compare the value measured with
Technical data
Degree of protection: IP 32
Ambient temperature
100
Installation – Vitotronic 300-K, MW1S
terminals.
terminals "1" and "2" of the plug.
Flow/return
Resistance
temperature
in Ω Ω Ω Ω
in °C / °F
30 / 86
569
40 / 104
592
60 / 140
643
the current temperature. If the
value differs significantly, check
installation and, if necessary,
replace sensor.
during operation:
0 to + 100 °C
32 to + 212 °F
during storage and transport:
–20 to + 170 °C
- 4 to + 158 °F