Coding 2
(cont.)
Coding in the factory setting
Multi-boiler control (cont.)
3b: 1
Autonomous boiler parallel connection with
supply temperature sensor
3C: 2 Net calorific strategy 2
(see page 110)
3d: 1
Output balance for gross calorific strategy and
net calorific strategy 1
3E: 0
Common supply pump ON/OFF subject to heat
demand
3F: 0
Without DHW tank priority for common supply
pump
General
40:12
Actuator operating time for isolation valve,
5
three-way mixing valve or mixing valve motor in
conjunction with permanent return temperature
control 125 seconds
Possible change
3b: 0
Autonomous boiler parallel connection
without supply temperature sensor
3b: 2
Autonomous boiler series connection
without supply temperature sensor
3b: 3
Autonomous boiler series connection with supply
temperature sensor
3b: 4
Sequential type of control with supply temperature
sensor
3C: 0
Gross calorific strategy
(see page 109)
3C: 1
Net calorific strategy 1
(see page 110)
3d: 0
No output statement
Please note:
Vitotronic 333, MW1S controls only in accordance
with net calorific strategy 2
3E: 1
Common supply pump OFF, if external disable
(plug aVD) is active
3F: 1
With DHW tank priority for common supply pump
40: 5
Operating time adjustable from 5 to 199 seconds
to
40:199
Coding – Vitotronic 300-K, MW1S
153