Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 160

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Coding – Vitotronic 300-K, MW1S
Coding 2
(cont.)
Coding in factory setting
General (cont.)
94: 0
Without plug-in adaptor for external safety
equipment
96: 1
With mixing valve extension Printed Circuit Board
97: 2
Outdoor temperature at sensor connected to
control unit will be transmitted via LON BUS to
control unit will be transmitted via LON BUS to
any connected Vitotronic 200-H
98: 1
Viessmann system number
(in conjunction with monitoring several systems
within one LON system with Vitocom 300)
Connection to terminals 2 and 3 in plug aVD
99: 0
(External disable/external mixing valve close)
(External disable/external mixing valve close)
inactive
inactive
160
Possible change
94: 1
With plug-in adaptor for external safety
equipment; will be recognised automatically
96: 0
Without mixing valve extension Printed Circuit
Board
97: 0
No transmission via LON BUS
97: 1
Outdoor temperature is adopted from LON BUS
98: 1
System number adjustable from 1 to 5
to
98: 5
Contact affects:
99: 1
No function
99: 2
Mixing valve close
Mixing valve circuit M2
99: 3
No function
99: 4
Mixing valve close
Mixing valve circuit M3
99: 5
No function
99: 6
Mixing valve close
Mixing valve circuits M2 and M3
99: 7
No function
99: 8
External disable
99: 9
No function
99: 10
External disable and
mixing valve close
Mixing valve circuit M2
99: 11
No function
99: 12
External disable and
mixing valve close
Mixing valve circuit M3
99: 13
No function
99: 14
External disable and
mixing valve close
Mixing valve circuits M2 and M3
99: 15
No function