Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 162

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Coding – Vitotronic 300-K, MW1S
Coding 2
(cont.)
Coding in factory setting
System circuit/mixing valve circuit
A0: 0 Without remote control
A2: 2 With DHW tank priority applicable to heating circuit
pump and mixing valve
pump and mixing valve
A3: 2 Outdoor temp. below 1 ˚C / 34 ˚F:
Heating circuit pump ON
Outdoor temp. above 3 ˚C / 37 ˚F:
Heating circuit pump OFF
For settings below 1 ˚C / 34 ˚F pipes outdoor
thermal insulation shell of building can freeze up,
particularly during standby mode, e.g. during
holidays.
A4: 0 With frost protection
162
Possible change
A0: 1
With Vitotrol 200
A0: 2
With Vitotrol 300
A2: 0
Without DHW tank priority applicable to
heating circuit pump and mixing valve
A2: 1
With DHW tank priority for mixing valve:
Mixing valve is closed during DHW heating;
heating circuit pump operates
A2: 3
Do not adjust
to
A2: 15
Heating circuit pump
(see back of manual for conversion chart)
A3: –9
ON at
OFF at
A3: –8
–10 ˚C
–8 ˚C
A3: –7
– 9 ˚C
–7 ˚C
A3: –6
– 8 ˚C
–6 ˚C
A3: –5
– 7 ˚C
–5 ˚C
– 6 ˚C
–4 ˚C
A3: –4
A3: –3
– 5 ˚C
–3 ˚C
A3: –2
– 4 ˚C
–2 ˚C
A3: –1
– 3 ˚C
–1 ˚C
– 2 ˚C
0 ˚C
A3: 0
A3: 1
– 1 ˚C
1 ˚C
A3: 2
0 ˚C
2 ˚C
to
1 ˚C
3 ˚C
A3: 15
to
14 ˚C
16 ˚C
A4: 1
No frost protection
Adjustment only possible if coding A3 : –9 is set.
Please observe note regarding coding
address A3.