Coding 1
(cont.)
Coding in the factory setting
Boiler/burner
06: 87 Maximum boiler water temperature limit
87 ˚C / 189 ˚F
Boiler
07: 1
Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
Burner (two stage/mod.) (see page 78)
*1
08:
Maximum burner output
in kW
*1
09:
Maximum burner output
in kW
*1
0A:
Burner base output
in percent
Burner (mod.) (see page 79)
15: 10 Burner actuator run time
10 seconds
General
40:12
Actuator operating time for isolation valve,
5
three-way mixing valve or mixing valve motor
in conjunction with return temperature control
125 seconds
77: 1
LON participant number
*1
The factory setting is defaulted by the boiler coding card.
Possible change
06: 20
Maximum boiler water temperature limit
to
adjustable from 20 to 127 ˚C / 68 to 261 ˚F
06:127
07: 2
Consecutive boiler number in multi-boiler systems
to
(in conjunction with coding address 01)
07: 4
08: 0
Maximum output adjustable from 0 to 199 kW;
to
1 setting step = 1 kW
08:199
09: 0
Maximum output adjustable from 0 to 19900 kW;
to
1 setting step = 100 kW
09:199
0A: 0
P
in kW
G
x 100
to
P
in kW
max
%
0A:100
= P
in %
G
P
Base output
G
P
Maximum output
max
15: 5
Operating time adjustable from 5 to 199 seconds
to
for Vitocrossal 300 with MatriX burner
15:199
Set
Type CM3 and CU3: 15 : 64
Type CV3: 15 : 19
40: 5
Operating time adjustable from 5 to 199 seconds
to
40:199
77: 2
LON participant number, adjustable from 1 to 99
to
Please note:
77: 99
Allocate each number only once.
Coding – Vitotronic 100, GC1
139