Coding – Vitotronic 100, GC1
Coding 2
(cont.)
Coding in the factory setting
Boiler
0C: 5 Isolation valve modulating independently
Isolation valve modulating independently
of set boiler water temperature
of set boiler water temperature
0d: 2
With Therm-Control, affects isolation valve
With Therm-Control, affects isolation valve
(function inactive, if 0C : 1 is programmed)
(function inactive, if 0C : 1 is programmed)
Boiler/burner
*1
13:
Shutdown differential in ˚C / ˚F
Shutdown differential in ˚C / ˚F
Burner is switched OFF when the set boiler
Burner is switched OFF when the set boiler
water temperature is exceeded
Burner
*1
14:
Minimum operating time in minutes
Burner (mod.) (see page 79)
15: 10 Burner actuator run time
10 seconds
*1
The factory setting is defaulted by the boiler coding card.
142
Possible change
0C: 0
No function
0C: 1
Constant control of return temperature
0C: 2
Controlled with time-delay isolation valve
0C: 3
Isolation valve controlled via boiler water
temperature
0C: 4
Isolation valve modulating subject to set
boiler water temperature
0d: 0
Without Therm-Control
0d: 1
With Therm-Control, affects mixing valves
of downstream heating circuits
13: 0
Without shutdown differential
13: 2
Shutdown differential adjustable from 2 to 20 ˚C /
3.6 to 36 ˚F
to
13: 20
14: 0
Minimum operating time adjustable from 0 to 15
to
minutes
14: 15
15: 5
Operating time adjustable from 5 to 199 seconds
to
for Vitocrossal 300 with MatriX burner
15:199
Set
Type CM3 and CU3: 15 : 64
Type CV3: 15 : 19