Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 157

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Coding 2
(cont.)
Coding in factory setting
DHW (cont.)
64: 2
During party mode and after external
changeover of operating program with
permanently normal room temperature:
Enable constant DHW heating enabled
and DHW recirculation pump ON
66: 4
Input of set DHW value:
at programming unit and all installed
Vitotrol 300 remote control units
Vitotrol 300 remote control units
rd
67: 0
Without a 3
set DHW set-point
temperature
68: 8
With 2 DHW tank temperature sensors
(coding 55 : 2):
DHW tank heating switch-off point
with set value × 0.8
69: 7
With 2 DHW tank temperature sensors
(coding 55 : 2):
DHW tank heating starting point with
set value × 0.7
70: 0
DHW recirculation pump ON acc. to time
program when DHW heating is enabled
71: 0
DHW recirculation pump:
ON acc. to time program
72: 0
73: 0
75: 0
DHW recirculation pump during
economy mode:
ON acc. to time program
Possible change
64: 0
No DHW heating, DHW recirculation pump OFF
64: 1
DHW heating and DHW recirculation pump acc. to time
program
66: 0
At programming unit
66: 1
At programming unit and remote control – system circuit A1
66: 2
At programming unit and remote control – mixing valve circuit
M2
66: 3
At programming unit and remote control – mixing valve circuit M3
66: 5
At remote control – system circuit A1
66: 6
At remote control mixing valve circuit M2
66: 7
At remote control – mixing valve circuit M3
With Vitosolic:
rd
67: 1
input of a 3
set DHW set point temperature; adjustable
to
from 1 to 95 ˚C / 34 to 203 ˚F
67: 95
Reloading suppression will be active below set temperature.
DHW tank is heated only by solar heating system.
68: 2
Factor adjustable
to
from 0.2 to 1;
68: 10
1 setting step = 0.1
69: 1
Factor adjustable
to
from 0.1 to 0.9;
69: 9
1 setting step = 0.1
70: 1
DHW recirculation pump ON according to time program
71: 1
OFF during DHW heating to first set value
71: 2
ON during DHW heating to first set value
72: 1
OFF during DHW heating to second set value
72: 2
ON during DHW heating to second set value
During time program
73: 1
1x/h ON for five minutes
to
to
73: 6
6x/h ON for five minutes
73: 7
Constantly ON
75: 1
OFF
Coding – Vitotronic 300-K, MW1S
157