Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 161

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Coding 2
(cont.)
Coding in factory setting
General (cont.)
9A: 0 Connection to terminals 1 and 2 in plug aVD
(External mixing valve open) inactive
(External mixing valve open) inactive
9b: 70 Set minimum supply temperature for external
Set minimum supply temperature for external
demand (input aVH)
demand (input aVH)
70 ˚C / 158 ˚F
9C: 20 Monitoring LON participants
9C: 20 Monitoring LON participants
When there is no response from a participant,
When there is no response from a participant,
values defaulted inside control unit continue to be
used for a further 20 min. Only then will a fault
message be triggered.
9d: 0
Without Input Module
0 to 10V
9F: 8
With mixing valve circuit:
Differential temperature 8 ˚C / 14.4 ˚F
Possible change
Contact affects:
9A: 1
No function
9A: 2
Mixing valve open
Mixing valve circuit M2
9A: 3
No function
9A: 4
Mixing valve open
Mixing valve circuit M3
9A: 5
No function
9A: 6
Mixing valve open
Mixing valve circuits M2 and M3
99: 7
No function
Input aVH blocked
9b: 0
Set temperature adjustable from 1 to 127 ˚C /
9b: 1
34 to 261 ˚F
to
9b:127
9C: 0
No monitoring
9C: 5
Time adjustable
to
from 5 to 60 minutes
9C: 60
9d: 1
With Input Module 0 - 10V;
will be recognized automatically
9F: 0
Differential temperature adjustable from 0 to 40 ˚C/
to
0 to 72 ˚F
9F: 40
Coding – Vitotronic 300-K, MW1S
161