Coding 2
(cont.)
Coding in factory setting
Mixing valve circuit
F1: 0
Slab curing function inactive
Systems/mixing valve circuit
F2: 8
Time limit for party mode 8 hours
*1
Party mode ends automatically with heating program r
Possible change
F1: 1
to
F1: 4
*1
F2: 0
F2: 1
to
F2: 12
r w
r
r
w when system changes over to operation with normal room temperature.
w
w
Coding – Vitotronic 300-K, MW1S
Slab curing function adjustable in accordance
with four optional temperature-time profiles
(see page 168)
Please note:
Observe slab curing supplier's instructions.
Observe local regulations.
Report to be provided by heating contractor
must contain following details:
Heat-up data with their respective supply
temperatures
Max. supply temperature achieved
Operating condition and outdoor temperature
during handover
Function continues after power failure or after
control unit has been switched OFF.
Heating program r
r w
w will be started, after
r
r
w
w
screed-drying function has been completed or
if address is manually set to 0.
No time limit for party mode
Time limit for party mode adjustable from 1 to
*1
12 hours
*1
167