Components from the parts list
LON communication module
Plug in the LON communication module into the control
unit. The communication interruption will be displayed.
D
Fixed high limit
In the factory setting set to
120 ˚C / 248 ˚F , adjustable to
110 or 99 ˚C / 230 ˚C or 212 ˚F
(see page 32)
Electromechanical temperature
switch according to the liquid
expansion principle; with lockout
Intrinsically safe; also lockout in case
of capillary tube leaks or ambient
temperatures below –10 ˚C / 14 ˚F
Limits the boiler water temperature
to the maximum permissible value by
shutdown and manual reset
Central mounting M 10, capillary
3600 mm / 142 inches long
Probe ∅ 3 mm / 0.1 inches,
180 mm/ 7 inches long
Tests:
effectiveness via test button
A
A
LON
LON LON
LON LON
C
B
B
Test button
For testing the fixed high limit.
For a description, see page 72.
Components – Vitotronic 100, GC1
A Control unit or Vitocom 300
A
B Interconnecting cable for data
LON
exchange between the control
units, part no. 7143 495
C Terminators, (standard delivery –
C
Vitotronic 300-K, MW1S)
D Slots for B and C
Adjustable high limit
In the factory setting set to 95 ˚C /
203 ˚F, adjustable to 100 or 110 ˚C
/ 212 or 230 ˚F (see page 32)
IMPORTANT
Adjust downwards at least 20 ˚C /
36 ˚F higher than the DHW
temperature, upwards at least 15 ˚C/
27 ˚F lower than the fixed high limit.
Electromechanical temperature
switch according to the liquid
expansion principle
Regulates the maximum boiler water
temperature (e.g. in emission test
mode)
Adjusting shaft 6 mm / 0.2 inches
half-round
Adjustment knob pushed on shaft
from front
Capillary 3600 mm / 142 inches long
Probe ∅ 3 mm / 0.1 inches, 180 mm/
7 inches long
Tests:
Effectiveness via emissions test
mode