Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 158

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Coding – Vitotronic 300-K, MW1S
Coding 2
(cont.)
Coding in factory setting
General
76: 0
Without communication module
77: 5
LON participant number
78: 1
Enable LON communication
79: 1
Control unit is fault manager
7A: 0 Without central control of heating circuits
7b: 1
Transmitting time via LON BUS
7F: 1
Detached house
80: 1
A fault message is issued,
A fault message is issued,
if a fault is active for at least 5 seconds
if a fault is active for at least 5 seconds
81: 1
Automatic daylight saving time changeover
Automatic daylight saving time changeover
Please note:
Please note:
Coding addresses 82 to 87 only feasible if
Coding addresses 82 to 87 only feasible if
coding 81 : 1 is set.
158
Possible change
76: 1
With LON communication module;
will be recognised automatically
77: 1
LON participant number, adjustable from 1 to 99
to
Please note:
77: 99
Allocate each number only once
78: 0
Disable LON communication
79: 0
Control unit is not fault manager
With central control of:
7A: 1
System boiler circuit A1
7A: 2
Mixing valve circuit M2
7A: 3
Mixing valve circuit M3
7b: 0
No transmission of time via LON BUS
7F: 0
Multi-occupancy house
80: 0
Immediate fault message
80: 2
Minimum fault duration before displaying a fault
to
message is adjustable from 10 to 995 seconds;
80:199
1 setting step = 5 seconds
81: 0
Manual changeover - daylight saving time
81: 2
81: 3
Accept time via LON