Viessmann Vitotronic 100 GC1 Installation And Service Instructions Manual page 141

Digital boiler control unit outdoor-reset logic digital cascade control, for installation in custom control panel
Table of Contents

Advertisement

Coding 2
(cont.)
Coding in the factory setting
Burner (mod.) (see page 79)
05: 70 Burner curve
Boiler/burner
06: 87 Maximum boiler water temperature limit
87 ˚C / 186 ˚F
Boiler
07: 1
Consecutive boiler number in multi-boiler systems
(in conjunction with coding address 01)
Burner (two stage/mod.) (see page 78)
*1
08:
Maximum burner output
in kW
*1
09:
Maximum burner output
in kW
*1
0A:
Burner base output
in percent
*1
The factory setting is defaulted by the boiler coding card.
Possible change
05: 0
Linear burner curve
05: 1
Non-linear burner curve
to
(see page 79):
05: 99
P
in kW
T
x 100
P
in kW
max
%
= P
in %
T
P
Partial load at 1/3
T
of the burner
actuator operating
time
P
Maximum output
max
06: 20
Maximum boiler water temperature limit
adjustable from 20 to 127 ˚C / 68 to 127 ˚F
to
06:127
07: 2
Consecutive boiler number in multi-boiler systems
to
(in conjunction with coding address 01)
07: 4
08: 0
Maximum output adjustable from 0 to 199 kW;
to
1 setting step = 1 kW
08:199
09: 0
Maximum output adjustable from 0 to 19900 kW;
to
1 setting step = 100 kW
09:199
0A: 0
P
in kW
G
x 100
to
P
in kW
max
%
0A:100
= P
in %
G
P
Base output
G
P
Maximum output
max
Coding – Vitotronic 100, GC1
141

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 300-k mw1s

Table of Contents