Parameter group compressor 2
Parameter group compressor 2
Service menu:
1. Press OK + å simultaneously for
approx. 4 s.
2. "Coding level 1"

5100 Enabling heat pump stage 2

"Enable 5100"
Enabling the heat pump stage 2 (type
BWS).
Valu
Explanation
e
"0"
Heat pump stage 2 is not used,
e.g. in the event of a fault or if the
output of stage 1 is permanently
sufficient.
"1"
Heat pump stage 2 is used.
5130 Heat pump output
"Output compressor stage 2 5130"
Type-dependent heating output of heat
pump stage 2.
Delivered condition
Setting range
186
3. "Compressor 2"
4. Select parameter.
Delivered condition
Setting
This value is required to calculate the
energy statement and seasonal perform-
ance factor.
Specified via coding card according to rated heating output
of heat pump stage 2 (e.g. 8 kW for type 108; see type plate
for rated heating output)
1 to 255 kW
0
0 / 1