Viessmann VITOCAL 300-G Installation And Service Instructions Manual page 208

Compact heat pump with electric drive single and two-stage, type bw/bws, ww/wws
Table of Contents

Advertisement

Parameter group heating circuits/cooling circuit
2003 Enabling the remote control
A Vitotrol 200 remote control unit can be
used for each heating circuit.
Vitotrol 200 installation instruc-
tions
Valu
Explanation
e
"0"
Remote control is not enabled.
"1"
Vitotrol 200 remote control for the
heating circuit is installed and
enabled.
2006/2007 Heating curve slope/level
"Heating curve slope 2006"
"Heating curve level 2007"
Heating curve level and slope for all
heating circuits (A1, M2 and M3).
Operating instructions
Delivered condition
Setting range
200A Influence of room temperature hook-up
"Slope room hook-up 200A"
208
Note
Remote control units have no function
when the heat pump is set to "Manual
mode".
Delivered condition
Setting
Note
The values determined from the heating
curves for the flow temperature are
transferred directly as set values for
heating circuits with mixers (M2, M3).
The set flow temperatures for the direct
heating circuit (A1) are always around 8
K higher than the values from the heating
curve.
"Heating curve level
2007"
0 (≙ 0 K)
–150 to +400
(≙ –15 to + 40 K)
(cont.)
"Heating curve slope
2006"
6 (≙ 0.6)
0 to 35
(≙ 0 to 3.5)
0
0 / 1