Parameter group electric heater
790A Stage at power-OFF
Valu
Explanation
e
"0"
Instantaneous heating water
heater remains off during power-
OFF, except for frost protection.
"1"
Output stage 1, e.g. 3 kW
"2"
Output stage 2, e.g. 6 kW
"3"
Output stage 3, or subject to type
and power connection, stages 1
and 2 simultaneously, e.g. 9 kW
790B Dual-mode temperature instantaneous heating water
heater
"Dual mode temperature, electric heater 790B"
Temperature limit for heating with the
instantaneous heating water heater (on
site).
If the long-term average outside temper-
ature falls below the dual-mode temper-
ature, the control unit enables operation
of the instantaneous heating water
heater. Above the dual-mode tempera-
ture, the control unit starts the instanta-
neous heating water heater only if the
heat pump develops a fault.
Delivered
100 (≙ 10 °C)
condition
Setting
–500 to +500
range
(≙ –50 to +50 °C)