Parameter group cooling
7101 Cooling circuit
"Cooling circuit 7101"
This parameter specifies whether cool-
ing occurs in one of the heating circuits
or in a separate cooling circuit.
Valu
Explanation
e
"1"
Cooling on heating circuit A1
"2"
Cooling on heating circuit M2
"3"
Cooling on heating circuit M3
"4"
Cooling a separate cooling cir-
cuit
7102 Room temperature separate cooling circuit
"Room temperature 7102"
With this parameter a different set room
temperature than for the heating circuits
can be specified for the separate cooling
circuit. This makes it possible, for exam-
ple, to also cool a storage room in winter,
independent of the set room tempera-
ture.
7103 Minimum flow temperature for separate cooling circuit
"Minimum flow temperature 7103"
If a lower set flow temperature than the
value specified here results due to out-
side and room temperatures according
to the cooling curve, the flow tempera-
ture is regulated to this value.
212
Note
Cooling mode is not possible for several
heating or cooling circuits simultane-
ously.
Delivered condition
Setting range
Operating instructions
Delivered
200 (≙ 20 °C)
condition
Setting
100 to 300
range
(≙ 10 to 30 °C)
Note
Only the set flow temperature is limited
with this value, not the actual tempera-
ture.
The minimum permissible set flow tem-
perature specified here applies both for
cooling a heating circuit as well as for
cooling a separate cooling circuit.
1
1 to 4