Commissioning/service reports
Control parameters report
Parameter
DHW
Cylinder temperature DHW
DHW with e heating
Minimum temperature
Maximum temperature
DHW hysteresis
Booster heater hysteresis
Start optimisation
Stop optimisation
Set temperature 2
Temperature sensor 2
Combi cylinder
No. of attempts DHW
Cylinder primary pump type
Solar
Solar control unit type
Electric heater
Inst. heating water heater
Heating with electro
Maximum stage, electric heating
Stage at power-OFF
Dual-mode temperature, electric heating 790B
Internal hydraulics
Heat pump for drying a building
Screed program
Heating/DHW diverter valve
Set flow temperature, external demand
Primary source type
Secondary pump type
Heating water buffer cylinder
Buffer cylinder
Fixed temperature
Hysteresis, buffer cylinder heating
Maximum temperature
Buffer cylinder fixed value mode temper-
ature limiter
238
(cont.)
Code
Delivered condi-
tion
6000
500 (≙ 50 °C)
6015
1
6005
100 (≙ 10 °C)
6006
600 (≙ 60 °C)
6007
70 (≙ 7 K)
6008
100 (≙ 10 K)
6009
0
600A
0
600C
600 (≙ 60 °C)
600E
No function
6016
0
6017
1
6020
Do not adjust.
7A00
0
7900
0
7902
1
7907
3
790A
0
100 (≙ 10 °C)
7300
0
7303
0
730D
0
730C
500 (≙ 50 °C)
7320
Do not adjust.
7340
Do not adjust.
7200
0
7202
500 (≙ 50 °C)
7203
50 (≙ 5 K)
7204
600 (≙ 60 °C)
7208
100 (≙ 10 °C)
Commis-
sioning