Connection and wiring diagrams
Overview of the PCBs and connection options
Message and safety connections
Terminals
Function
X3.1
Phase switched
X3.2
External blocking, mixer
X3.14
CLOSED
or to exter-
nal exten-
sion H1
X3.3
Flow switch, well circuit
X3.4
X3.6
Power-OFF
X3.7
X3.8
Primary circuit pressure
X3.9
switch and/or frost stat
or
Jumper
X3.10
Fault message, lag heat
X3.11
pump in a cascade
or
Jumper
226
Explanation
Zero volt contact required:
■ Closed: Blocking enabled
■ Open: No blocking
■ Breaking capacity 230 V~, 2 mA
Connect on site
Zero volt contact required:
■ Closed: Heat pump operational
■ Open: Heat pump shut down
■ Breaking capacity 230 V~, 0.15 A
Connection on site; remove jumper when
connecting
Zero volt contact required:
■ Closed: No blocking (safety chain has
continuity)
■ Open: Blocking enabled
■ Breaking capacity 230 V~, 0.15 A
Connection on site; remove jumper when
connecting
Zero volt contact required:
■ Closed: Safety chain has continuity
■ Open: Safety chain interrupted; heat
pump shut down
■ Breaking capacity 230 V~, 0.15 A
Connect on site:
■ Connected in series if both safety com-
ponents are installed
■ Insert jumper if no safety compo-
nents are installed
Zero volt contact required:
■ Closed: No faults
■ Open: Fault
■ Breaking capacity 230 V~, 0.15 A
Connection on site; remove jumper when
connecting
(cont.)