Viessmann VITOCAL 300-G Installation And Service Instructions Manual page 143

Compact heat pump with electric drive single and two-stage, type bw/bws, ww/wws
Table of Contents

Advertisement

Messages
(cont.)
Message
System characteristics Cause
CA Primary source
CB Primary temperature
Heat pump stops.
CC Coding card
CD KM BUS Vitocom
Primary circuit fault:
■ Primary circuit pres-
sure switch/frost pro-
tection monitoring has
responded
■ Primary pump thermal
circuit breaker (heat
pump stage 1,
type BW or common
primary pump)
Min. primary flow tem-
perature (brine inlet) not
achieved
The coding card cannot
be read
Communication error -
KM BUS Vitocom 100
Troubleshooting
Measures
■ Check safety equip-
ment on cross connect
PCB, terminals X3.9
and X3.8; in systems
without safety equip-
ment, check jumper
between X3.9/X3.8.
■ Reset thermal relay,
check primary pump
and replace if required
The switching signal can
be tested at connection
215.3.
Check primary circuit for
flow rate.
■ Check coding card and
replace if required.
■ Check controller and
sensor PCB and
replace, if required.
Check Vitocom 100 con-
nections and connecting
cables.
Check connections at the
controller and sensor
PCB, plug aVG KM BUS.
A fluctuating DC voltage
between approx. 20 V and
30 V can be measured at
the terminals.
143