Parameter group internal hydraulics
7303 Screed program
■ The screed programme affects all ena-
bled heating circuits in parallel.
■ The selected "Screed program" is
continued after a power failure or after
the control unit has been switched off.
■ The selected operating programme
continues if the "Screed program"
has terminated in accordance with the
programme or, before its expiry, the
temperature/time profile "0" is selec-
ted.
■ The temperature/time profiles 7 to 12
regulate to the maximum flow temper-
ature.
■ If the time profile has a higher set flow
temperature, the set temperature is
limited by parameter "Maximum flow
temperature 200E" (see page 209)
for the heating circuit.
■ The power consumption increases
when using an instantaneous heating
water heater (accessory) for drying
buildings.
Note
Observe the specifications of
EN 1264-4. The report to be provided by
the heating contractor must contain the
following heat-up details:
■ Heat-up data with respective flow tem-
peratures
■ Max. flow temperature achieved
■ Operating condition and outside tem-
perature during handover
200
(cont.)
Valu
e
"0"
"1"
"2"
"3"
Temperature:time profile
A Flow temperature
B Days
No temperature/time profile
Termination of the current profile
and operation continued in heat-
ing or cooling mode.
Temperature/time profile 1 (in
acc. with EN 1264-4)
A
50
40
30
20
10
1
5
10
15
Temperature/time profile 2 (to
ZV parquet and flooring tech-
nology)
A
50
40
30
20
10
1
5
10
15
Temperature/time profile 3 (to
ÖNORM)
A
50
40
30
20
10
1
5
10
15
20
25
30
B
20
25
30
B
20
25
30
B