Reducing Inverter Overheating Pre-Alarm Warning Levels

The Inverter detects the temperature of the cooling fins using the thermistor, and protects the Inverter from
overheating. You can receive Inverter overheating pre-alarms in units of 10
The following overheating pre-alarm warnings are available: Stopping the Inverter as error protection, and
continuing operation, with the alarm OH (Radiation fins overheating) on the Digital Operator flashing.
Related Constants
Con-
stant
Number
L8-02
L8-03
* The factory setting depends upon the Inverter capacity. The value for 200 V Class Inverter of 0.4 kW is given.
-72
6
Name
Description
Display
Overheat pre-
Sets the detection temperature for
alarm level
the Inverter overheat detection
pre-alarm in °C.
The pre-alarm detects when the
OH Pre-Alarm
heatsink temperature reaches the
Lvl
set value.
Operation
Sets the operation for when the
selection after
Inverter overheat pre-alarm goes
overheat pre-
ON.
alarm
0: Decelerate to stop in
deceleration time C1-02.
1: Coast to stop
2: Fast stop in fast-stop time C1-
09.
OH Pre-Alarm
3: Continue operation (Monitor
Sel
display only.)
A fault will be given in setting 0
to 2 and a minor fault will be
given in setting 3.
°
C.
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
50 to
95 °C*
No
A
130
0 to 3
3
No
A
Control Methods
Open
Open
V/f
Flux
Loop
Loop
with
Vec-
Vector
Vector
PG
tor
1
2
A
A
A
A
A
A
A
A