Blocking Inverter Outputs (Baseblock Commands)

Set 8 or 9 (Baseblock command NO/NC) in one of the constants H1-01 to H1-10 (multi-function contact input
terminal S3 to S12 function selection) to perform baseblock commands using the terminal's ON/OFF opera-
tion, and prohibit Inverter output using the baseblock commands.
Clear the baseblock command to restart the operating using speed search from frequency references from the
previous baseblock command input.
Multi-function Contact Inputs (H1-01 to H1-10)
Set-
ting
Value
8
External baseblock NO (NO contact: Baseblock at ON)
9
External baseblock NC (NC contact: Baseblock at OFF)
Time Chart
The time chart when using baseblock commands is shown below.
Forward operation/Stop
IMPORTANT
-74
6
Baseblock command
Frequency reference
Output frequency
Fig 6.48 Baseblock Commands
If using baseblock commands with a variable load, do not frequently input baseblock commands during oper-
ation, as this may cause the motor to suddenly start coasting, and may result in the motor falling or slipping.
Function
Input Cleared
Search from stored frequency reference
Hold
Control Methods
Open
Open
V/f
Loop
Flux
Loop
V/f
with
Vec-
Vec-
Vec-
PG
tor
tor
tor
1
2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes