Using A Digital Reference Board - YASKAWA Varispeed CIMR-G7A Instruction Manual

General purpose inverter (advanced vector control) 200v/400v class 0.4 to 110/300 kw (1.2 to 160kva) (1.04 to 460kva)
Hide thumbs Also See for Varispeed CIMR-G7A:
Table of Contents

Advertisement

Related Constants
Con-
stant
Number
F2-01
Setting Precautions
Always set b1-01 (Reference selection) to 1 (control circuit terminal) when using the AI-14B for three chan-
nels of independent inputs. When this is done, H1-01 to H1-10 (multi-function contact inputs) cannot be set to
2 (Option/Inverter selection).

Using a Digital Reference Board

When using a DI-08 or DI-16H2 Digital Reference Board, set b1-01 (Reference selection) to 3 (Option board).
The DI-16H2 can be used to set a frequency using a 16-bit digital reference. The DI-08 can be used to set a
frequency using a 8-bit digital reference.
Related Constants
Con-
stant
Number
F3-01
-160
6
Name
Description
Display
Bi-polar or uni-
Sets the functions for channel 1 to
polar input
3 that are effective when the AI-
selection
14B Analog Reference Board is
used.
0: 3-channel individual (Chan-
nel 1: terminal A1, Channel 2:
terminal A2, Channel 3: termi-
nal A3)
1: 3-channel addition (Addition
AI-14 Input Sel
values are the frequency refer-
ence)
When set to 0, select 1 for b1-01.
In this case the multi-function
input "Option/Inverter selection"
cannot be used.
Name
Description
Display
Digital input
Sets the Digital Reference Board
option
input method.
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1 Hz unit
4: BCD 0.1 Hz unit
5: BCD 0.01 Hz unit
6: BCD special setting (5-digit
input)
DI Input
7: Binary input
6 is only effective when the DI-
16H2 is used.
When o1-03 is set to 2 or higher,
the input will be BCD, and the
units will change to the o1-03 set-
ting.
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 or 1
0
No
A
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 7
0
No
A
Control Methods
Open
Open
V/f
Flux
Loop
Loop
with
Vec-
Vector
Vector
PG
tor
1
2
A
A
A
A
Control Methods
Open
Open
V/f
Flux
Loop
Loop
with
Vec-
Vector
Vector
PG
tor
1
2
A
A
A
A