I
NSTALLATION
P
16
AGE
Clearances to Combustibles
!
Follow the clearances listed below - do not follow the clearances listed in the chimney instructions
•
Maintain a 2" clearance from the chimney to combustibles (measured horizontally)
•
Use offsets, if necessary, to maintain clearances
•
In the area above the fireplace before the chimney penetrates the ceiling (use a firestop), the chimney
must maintain the clearances listed below:
5" to the rear of the chimney
4-1/2" to the front of the chimney
Min. 2" clearance to
the sides with offsets
Min. 4-1/2" clearance
Firestops
•
Whenever the chimney penetrates a floor or
ceiling a firestop is required on the bottom side
of the floor joists
•
When passing through an attic the firestop must
be placed on the attic side of the joists
•
When the chimney passes through a living space
it must be totally enclosed (maintain the
minimum 2" clearance to combustibles)
•
The space between frames that hold the firestop
in place should be measured as follows:
Temco
Superior
FMI
Marco
( C
ONTINUED
Firestop
to the front.
16"
16 1/2"
16 1/2"
16 1/2"
)
Min. Clearance 2" (from this
point upwards)
Min. 5" clearance
to the rear.
The fireplace enclosure must not be
less than 81" above the base of the
fireplace.
• If the fireplace is raised, the
enclosure height must be raised to
maintain the 81".
• Do not build into this area.
• Do not slope the walls inward.
• The header, vertical framing
members, and all interior wall
surfaces may protrude a maximum
4" into this area.
NOTE:
Many firestops are
designed for a 1"
clearance, this fireplace
requires a 2" clearance.
Space
between
frames
Firestop