Installing the Switch Chassis
Step 1
Attach the two cable management frames to the chassis as follows:
a) Position one of the cable management side frame assemblies on the vertical mounting bracket attached to one side
of the front of the chassis so that the following screw holes align:
• Five screw holes in the assembly should align with the screw holes in five studs on the mounting bracket (see
the following figure).
Figure 15: Attaching a Cable Management Assembly to the Chassis
1
2
• Four screw holes in the two angled brackets on the assembly should align with the four screw holes in the
chassis. If these screw holes do not align together or the angled brackets do not touch the chassis, try positioning
the assembly on the opposite side of the chassis.
b) Secure the upper portion of the frame to the chassis vertical mounting bracket with three M4 x 12 mm, flat-head,
Phillips screws. Tighten each screw to 11.5 to 15 in-lb (1.3 to 1.7 N·m) of torque.
c) Secure the bottom portion of the frame to the chassis using four M4 x 12 MM flat-head Phillips screws in the two
angled brackets on the frame. Tighten each screw to 11.5 to 15 in-lb (1.3 to 1.7 N·m) of torque.
OL-31330-01
◦ 22 M4 x 12-mm, flat-head, Phillips screws
Vertical mounting bracket on the chassis
Cable management assembly
Installing Cable Management Frames onto the Chassis
3
M4 x 12 mm screws (three) secure the upper
portion of assembly to the mounting bracket
4
M4 x 12 mm screws (four) secure two angle
brackets to the chassis
Cisco Nexus 7706 Hardware Installation Guide