Installing the Switch Chassis
• Verify that the data center ground is accessible where you are installing the chassis.
• Verify that you have the following tools and equipment:
You should also have at least two persons to push the chassis when you slide it onto the rack.
Note
To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to
ensure that the system remains stable. The following guidelines are provided to ensure your safety:
• This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
• When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the
• If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the
Statement 1006
Step 1
If you need to make the chassis as light as possible for moving, you can optionally remove the fabric modules, fan trays,
and power supplies.
• To remove a power supply, follow these steps:
1 Slide the handle in the middle of the ejector lever towards the end of the lever and rotate the lever away from
the power supply.
2 Pull the power supply a couple of inches (about 5 cm) out of the chassis.
OL-31330-01
◦ Mechanical lift capable of lifting the full weight of the chassis and its installed modules
Fully loaded, the chassis can weigh up to 325 lb (147.5 kg). You can lighten the chassis
Note
for easier moving by removing its power supplies, fan trays, and fabric modules. To
determine the full weight of the chassis and the appropriate weight rating for the
mechanical lift, see
Power Supplies, on page
You must use a mechanical lift or floor jack to elevate a switch weighing over 120
Caution
pounds (55 kg).
◦ Phillips-head torque screwdriver
◦ Bottom-support rails kit (shipped with the accessory kit)
Part of this kit has already been used to install the bottom-support rails. You should still have 14
12-24 x 3/4-inch or M6 x 19 mm Phillips screws, which are required for attaching the chassis to
the rack.
heaviest component at the bottom of the rack.
unit in the rack.
Installing the Chassis on a Four-Post Rack or Cabinet
Weights and Quantities for the Chassis, Modules, Fan Trays, and
98.
Cisco Nexus 7706 Hardware Installation Guide
25