3-2 Test Run Operation

Parameter Initialization

•Initialize the parameters using the following procedure.
•To initialize the parameters, set parameter b084 to "02".
Key sequence
3
(In 1 s)
3-5
Display example
k0.0
Power On
Press the Mode key once, and then press the Decrement key three
bk-k-k-
times to display "b---".
Press the Mode key.
bk0k0k1
"b001" is displayed.
bk0k8k4
Use the Increment or Decrement key to display "b084".
0k0
Press the Mode key. The set value in "b084" is displayed.
0k2
Use the Increment or Decrement key to display "02".
bk0k8k4
Press the Enter key. The set value is entered and "b084" is displayed.
Press the STOP/RESET key while holding down the Mode and
Decrement keys simultaneously.
When the display blinks, release the STOP/RESET key first, and then
the Mode and Decrement keys.
=k.k0k0
Displays initialization.
dk0k0k1
The parameter number is displayed again in approximately 1 s.
Description