4-2 Function Mode
•The disconnection detection signal is output if the frequency reference of the external analog input
remains below the starting frequency for 500 ms.
•The signal stops 500 ms after the frequency reference has exceeded the starting frequency.
•Helps detect disconnection when a frequency reference is issued from the external analog inputs
(FV, FI) with the frequency reference selection set to the terminal (A001 = 01).
•Enabled only when the external analog inputs (FV, FI) are selected.
Example 1: Disabled in multi-step speed operation even when the frequency reference is set to
Example 2: Disabled even when the AT terminal selection is set to the FV/volume selection
4

PID FB Status Output

When the PID function is used, this function outputs a signal according to the FB value, as illustrated
below.
This is effective as a RUN command in operating multiple pumps.
Data
07
Available input terminals
Required settings
PID FB
upper limit
(C052)
PID FB
lower limit
(C053)
4-67
the external analog input (A001 = 01).
(A005 = 02) or FI/volume selection (A005 = 03) since the frequency reference is set
on the Digital Operator (volume) with the AT terminal turned on.
Starting
frequency
0Hz
External analog
OFF
input disconnection
detection (DC)
500 ms
Symbol
Function name
FBV
PID FB status output
PID FB value
FW
ON
FBV
ON
OFF
External analog input
frequency reference (FV, FI)
ON
500 ms
Status
See the figure below.
ON
Shifts output when exceeding the upper limit or
OFF
falling below the lower limit.
P1-PC, MA-MC (or MB-MC)
C021, C026, C052, C053
ON
Description
OFF at output frequency = 0