3-1 Test Run Procedure

3-1 Test Run Procedure
Item
Installation and Mounting Install the Inverter according to the installation conditions.
3
Wiring and Connection
Power On
Display Status Check
Parameter Initialization Initialize the parameters.
Parameter Settings
No-load Operation
Actual Load Operation
Operation
3-3
•Make sure that the installation conditions are met.
Connect to the power supply and peripheral devices.
•Select peripheral devices that meet the specifications, and wire correctly.
Check the following before turning on the power.
•Make sure that an appropriate power supply voltage is supplied and that the power input
terminals (R/L1, S/L2, and T/L3) are wired correctly.
3G3JX-A2 : 3-phase 200 to 240 V AC
3G3JX-AE : 1/3-phase 200 to 240 V AC
(Connect to L1 and N/L3 for 1 phase)
3G3JX-A4 : 3-phase 380 to 480 V AC
•Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the
motor correctly.
•Make sure that the control circuit terminals and the control device are wired correctly
and that all control terminals are turned off.
•Set the motor to no-load status (i.e., not connected to the mechanical system).
•After checking the above, turn on the power.
Make sure that there are no faults in the Inverter.
•When the power is turned on normally, the display shows:
RUN LED indicator
POWER LED indicator : ON
Volume LED indicator : ON
Data display
•If an error occurs, the error code is displayed on the data display. In this case, refer to
"Chapter 5 Maintenance Operations" and make the necessary changes to remedy.
•Set parameter No. b084 to "02", and press the
keys simultaneously.
Set the parameters required for a test run.
•Set the motor capacity selection (H003) and the motor pole number selection (H004).
Start the no-load motor via the Digital Operator.
•Use the FREQ adjuster on the Digital Operator to rotate the motor.
Connect the mechanical system and operate via the Digital Operator.
•If there is no problem with the no-load operation, connect the mechanical system to the
motor and operate via the Digital Operator.
Refer to "Chapter 4 Functions"
Description
: ON
ALARM LED indicator
RUN command LED indicator
Data LED indicator (frequency) : ON
: Displays the set value in d001.
key while holding down the
, and set the necessary parameters.
Reference page
2-1
2-6
: OFF
: ON
and