Explanation Of The Main Circuit Terminal Connection - Omron 3G3JX User Manual

Sysdrive jx series compact simplified inverters
Hide thumbs Also See for 3G3JX:
Table of Contents

Advertisement

2-2 Wiring
Model
(3G3JX-)
2
Main circuit
Control circuit
Relay
Ground
Screw Tightening Torque
Screw
M2
0.2 N•m (max. 0.25 N•m)
M2.5
0.5 N•m (max. 0.6N•m)
M3.5
0.8 N•m (max. 0.9 N•m)
M4
1.2 N•m (max. 1.3 N•m)
M5
3.0 N•m (max. 3.3 N•m)

Explanation of the Main Circuit Terminal Connection

Terminal
Terminal name
symbol
R/L1, S/L2,
Main power supply
T/L3 *
input terminal
U/T1,
Inverter output
V/T2, W/T3
terminal
+1,
External DC reactor
P/+2
terminal
Regenerative
P/+2, N/-
braking unit
connection terminal
Ground terminal
*
For 3G3JX-AE
Connect a single-phase 200-V AC input to terminals L1 and N/L3.
2-15
A2002 to A2007
AE002 to AE004
Screw size
W (mm)
M3.5
7.1
M2
M2.5
M4
Tightening torque
Connect the input power supply.
Connect to the motor.
Normally connected by the short-circuit
bar. Remove the short-circuit bar
between +1 and P/+2 when a DC reactor
is connected.
Connect optional regenerative braking
units.
(If a braking torque is required)
Ground (Connect to ground to prevent
electric shock and reduce noise.)
's terminal symbols, R/L1 corresponds to L1, S/L2 to L2, and T/L3 to N/L3.
A2015 to A2037
A4004 to A4037
AE007 to AE022
Screw size
W (mm)
M4
9.2
M2
M2.5
M4
Function
Do not remove the short-circuit bar
between +1 and P/+2 when a DC
reactor is not connected.
A2055 to A2075
A4055 to A4075
Screw size
W (mm)
M5
13
M2
M2.5
M5
13
Connection example
Motor
ELB
Power supply

Hide quick links:

Advertisement

Table of Contents
loading