7) Note the cooling method when the inverter is installed in an enclosure.
When two or more inverters are installed or a ventilation fan is mounted in an
enclosure, the inverters and ventilation fan must be installed in proper positions with
extreme care taken to keep the ambient temperatures of the inverters with the
permissible values. If they are installed in improper positions, the ambient
temperatures of the inverters will rise and ventilation effect will be reduced.
8) Install the inverter securely in the vertical direction with screws or bolts.
3) Note on ambient
temperatures
5cm
FR-E500
(1.97inch)
5cm
Measurement position
(1.97inch)
7) For installation in an enclosure
Ventilation
fan
Inverter
(Correct example)
Position of Ventilation Fan
8) Vertical mounting
4) Clearances around the inverter
Measurement
position
5cm
1cm (0.39inch)
(1.97inch)
or more*
These clearances are also necessary for changing the cooling fan.
Inverter
(Incorrect example)
INSTALLATION AND WIRING
10cm (3.94inch)
or more
1cm (0.39inch)
FR-E500
or more*
10cm (3.94inch)
or more
*5cm (1.97inch) or more for 5.5K and 7.5K
Inverter
Inverter
Built-in cooling fan
(Correct example)
When more than one inverter is contained
13
Leave sufficient
Cooling air
clearances above
and under the
inverter to ensure
adequate ventilation.
Cooling fan
built in the
inverter
Inverter
Inverter
(Incorrect example)
2